feat(micromate): one opcode table and a send-side gate -- writes refused unless allowed, 0xA2 always
micromate/opcodes.py holds WRITE_SUBS and the cross-series collision 0xA2.
MicromateProtocol._send reads the SUB of the bytes about to go out
(framing.request_sub) and refuses any write SUB not in allowed_writes, and
0xA2 unconditionally. Docstrings now say the reads-only policy is enforced.
request_sub also refuses any frame not in canonical form
(stuff(unstuff(body)) == body): an interior unescaped 02/03/04, a 10 XX
outside {02,03,04,10}, or a trailing lone DLE. What the gate checks is then
exactly what the unit parses.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
This commit is contained in:
1 parent
151ba1546f
commit
a3e4e85dfd
6 files changed
+178
-9
No files matched your search
+20
-8
@@ -4,13 +4,16 @@ protocol.py — one method per Micromate (Series IV) wire command.
|
||||
Returns raw payload bytes. Interpretation belongs in ``client.py``; this layer
|
||||
knows frames, offsets and sequencing, and nothing about what a field means.
|
||||
|
||||
Scope: **reads only.** Nothing here writes, erases, or changes monitoring
|
||||
state. That is deliberate and worth keeping — no command has ever been
|
||||
originated against a unit by this project; every write in
|
||||
``docs/micromate_protocol_reference.md`` was performed by THOR while we
|
||||
recorded. The first thing this codebase ever sends to a customer's instrument
|
||||
should be a decision someone made on purpose, not a side effect of a client
|
||||
that grew a method.
|
||||
Scope: **reads only on the wire, enforced.** Every outgoing frame passes
|
||||
`micromate.opcodes.check_transmit()` in `_send`: a write opcode is refused
|
||||
unless this connection was constructed with it in `allowed_writes` (nothing in
|
||||
the codebase does so yet), and `0xA2` -- CONFIRM ERASE on Series III -- is
|
||||
refused always. No command has ever been originated against a unit by this
|
||||
project; every write in ``docs/micromate_protocol_reference.md`` was performed
|
||||
by THOR while we recorded. The first thing this codebase ever sends to a
|
||||
customer's instrument should be a decision someone made on purpose, not a side
|
||||
effect of a client that grew a method. Write frames are *built* in
|
||||
``micromate.writes`` as reviewable plans; building one sends nothing.
|
||||
|
||||
Every offset and params layout below was read off THOR's own frames in
|
||||
``bridges/captures/9-24-26 - micromate2/`` rather than taken from the spec
|
||||
@@ -43,7 +46,8 @@ from typing import Optional
|
||||
|
||||
from minimateplus.transport import BaseTransport
|
||||
|
||||
from .framing import MicromateFrame, MicromateFrameParser, build_request
|
||||
from .framing import MicromateFrame, MicromateFrameParser, build_request, request_sub
|
||||
from .opcodes import check_transmit
|
||||
|
||||
log = logging.getLogger(__name__)
|
||||
|
||||
@@ -243,9 +247,13 @@ class MicromateProtocol:
|
||||
transport: BaseTransport,
|
||||
recv_timeout: float = DEFAULT_RECV_TIMEOUT,
|
||||
strict_checksums: bool = True,
|
||||
allowed_writes: frozenset = frozenset(),
|
||||
) -> None:
|
||||
"""
|
||||
Args:
|
||||
allowed_writes: write SUBs this connection may transmit. Empty by
|
||||
default -- every write opcode in `micromate.opcodes` is refused
|
||||
at `_send`, and `0xA2` is refused whatever this says.
|
||||
strict_checksums: raise on a bad checksum. **Defaults to True,
|
||||
unlike the Series III sibling**, which logs and continues
|
||||
because its parser cannot reliably tell an inner-frame
|
||||
@@ -262,6 +270,7 @@ class MicromateProtocol:
|
||||
self._transport = transport
|
||||
self._recv_timeout = recv_timeout
|
||||
self._strict = strict_checksums
|
||||
self._allowed_writes = frozenset(allowed_writes)
|
||||
self._parser = MicromateFrameParser()
|
||||
self._pending: list[MicromateFrame] = []
|
||||
|
||||
@@ -509,6 +518,9 @@ class MicromateProtocol:
|
||||
reset_parser=False)
|
||||
|
||||
def _send(self, frame: bytes) -> None:
|
||||
# The gate sees the bytes that are about to go out, not the caller's
|
||||
# intent: every transmit in this package passes through here.
|
||||
check_transmit(request_sub(frame), self._allowed_writes)
|
||||
log.debug("TX %d bytes: %s", len(frame), frame.hex())
|
||||
self._transport.write(frame)
|
||||
|
||||
|
||||