feat(micromate): one opcode table and a send-side gate -- writes refused unless allowed, 0xA2 always

micromate/opcodes.py holds WRITE_SUBS and the cross-series collision 0xA2.
MicromateProtocol._send reads the SUB of the bytes about to go out
(framing.request_sub) and refuses any write SUB not in allowed_writes, and
0xA2 unconditionally.  Docstrings now say the reads-only policy is enforced.

request_sub also refuses any frame not in canonical form
(stuff(unstuff(body)) == body): an interior unescaped 02/03/04, a 10 XX
outside {02,03,04,10}, or a trailing lone DLE.  What the gate checks is then
exactly what the unit parses.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
This commit is contained in:
serversdownandClaude Opus 5.5 committed 2026-10-22 17:10:23 -04:00
1 parent 151ba1546f
commit a3e4e85dfd
6 files changed
+178 -9

No files matched your search

+2 -1
View File
@@ -2,7 +2,8 @@
client.py — high-level API for a live Micromate (Series IV). client.py — high-level API for a live Micromate (Series IV).
Owns the transport, turns raw payloads into models. Read-only, like the layer Owns the transport, turns raw payloads into models. Read-only, like the layer
below it: nothing here writes, erases, or changes monitoring state. below it: nothing here writes, erases, or changes monitoring state, and the
protocol's opcode gate (`micromate.opcodes`) enforces that in code.
with MicromateClient(TcpTransport("63.45.161.30", 9034)) as mm: with MicromateClient(TcpTransport("63.45.161.30", 9034)) as mm:
info = mm.connect() info = mm.connect()
+6
View File
@@ -182,6 +182,12 @@ def request_sub(frame: bytes) -> int:
body = unstuff(frame[2:-1]) body = unstuff(frame[2:-1])
if len(body) < 17 or body[0] != MM_CMD: if len(body) < 17 or body[0] != MM_CMD:
raise ValueError(f"not a host->unit request frame: {bytes(frame[:8]).hex()}") raise ValueError(f"not a host->unit request frame: {bytes(frame[:8]).hex()}")
# Canonical form only: what this check reads must be exactly what the unit
# parses. An unescaped 02/03/04, a `10 XX` outside {02,03,04,10} or a
# trailing lone DLE would be read one way here and another by the unit.
if stuff(body) != frame[2:-1]:
raise ValueError(
f"not a canonical request frame (stuffing differs): {bytes(frame[:8]).hex()}")
return body[2] return body[2]
+58
View File
@@ -0,0 +1,58 @@
"""Micromate (Series IV) opcode table: which SUBs write, and which collide.
One place, as the parity spec requires. `MicromateProtocol._send` consults it
on every outgoing frame, so a write cannot reach a unit by a path nobody
thought about -- a scratch tool calling `protocol._send`, a hand-built frame, a
method added later.
Every SUB here was seen as a host->unit request in THOR's captures
(`docs/micromate_protocol_reference.md`). The table classifies REQUESTS: a few
of these values are also ACK SUBs of other commands (0x71 acks 0x8E, 0x72 acks
0x8D), which is irrelevant to a send-side check.
"""
from __future__ import annotations
from typing import Dict, FrozenSet
WRITE_SUBS: Dict[int, str] = {
0x47: "scheduler enable/disable",
0x68: "setup push: preferences block (0x08)",
0x71: "setup push: setup block (0x1A)",
0x72: "setup push: setup confirm",
0x73: "setup push: preferences confirm",
0x7E: "call-home config write (0x2C)",
0x7F: "call-home config confirm",
0x82: "setup push: trigger block (0x2E)",
0x83: "setup push: trigger confirm",
0x8D: "file open for write",
0x8E: "file body write",
0x96: "start monitoring",
0x97: "stop monitoring",
0xA2: "end call-home",
0xA8: "delete one event",
0xAA: "delete-event confirm",
0xDA: "setup push: file name",
}
# Same bytes, opposite consequence on the other series. Never transmitted on
# Series IV, allowed or not: if a Series-III unit is at the address (a moved
# modem, a stale IP), it would execute the other meaning. Lifting an entry is
# a spec change, not a parameter.
CROSS_SERIES_COLLISIONS: Dict[int, str] = {
0xA2: "CONFIRM ERASE on Series III -- erases every stored event; "
"'end call-home' on Series IV",
}
class OpcodeRefused(RuntimeError):
"""A frame was stopped before it reached the wire."""
def check_transmit(sub: int, allowed_writes: FrozenSet[int] = frozenset()) -> None:
if sub in CROSS_SERIES_COLLISIONS:
raise OpcodeRefused(
f"refused to transmit SUB 0x{sub:02X}: {CROSS_SERIES_COLLISIONS[sub]}")
if sub in WRITE_SUBS and sub not in allowed_writes:
raise OpcodeRefused(
f"refused to transmit SUB 0x{sub:02X} ({WRITE_SUBS[sub]}): writes are "
"not enabled on this connection")
+20 -8
View File
@@ -4,13 +4,16 @@ protocol.py — one method per Micromate (Series IV) wire command.
Returns raw payload bytes. Interpretation belongs in ``client.py``; this layer Returns raw payload bytes. Interpretation belongs in ``client.py``; this layer
knows frames, offsets and sequencing, and nothing about what a field means. knows frames, offsets and sequencing, and nothing about what a field means.
Scope: **reads only.** Nothing here writes, erases, or changes monitoring Scope: **reads only on the wire, enforced.** Every outgoing frame passes
state. That is deliberate and worth keeping — no command has ever been `micromate.opcodes.check_transmit()` in `_send`: a write opcode is refused
originated against a unit by this project; every write in unless this connection was constructed with it in `allowed_writes` (nothing in
``docs/micromate_protocol_reference.md`` was performed by THOR while we the codebase does so yet), and `0xA2` -- CONFIRM ERASE on Series III -- is
recorded. The first thing this codebase ever sends to a customer's instrument refused always. No command has ever been originated against a unit by this
should be a decision someone made on purpose, not a side effect of a client project; every write in ``docs/micromate_protocol_reference.md`` was performed
that grew a method. by THOR while we recorded. The first thing this codebase ever sends to a
customer's instrument should be a decision someone made on purpose, not a side
effect of a client that grew a method. Write frames are *built* in
``micromate.writes`` as reviewable plans; building one sends nothing.
Every offset and params layout below was read off THOR's own frames in Every offset and params layout below was read off THOR's own frames in
``bridges/captures/9-24-26 - micromate2/`` rather than taken from the spec ``bridges/captures/9-24-26 - micromate2/`` rather than taken from the spec
@@ -43,7 +46,8 @@ from typing import Optional
from minimateplus.transport import BaseTransport from minimateplus.transport import BaseTransport
from .framing import MicromateFrame, MicromateFrameParser, build_request from .framing import MicromateFrame, MicromateFrameParser, build_request, request_sub
from .opcodes import check_transmit
log = logging.getLogger(__name__) log = logging.getLogger(__name__)
@@ -243,9 +247,13 @@ class MicromateProtocol:
transport: BaseTransport, transport: BaseTransport,
recv_timeout: float = DEFAULT_RECV_TIMEOUT, recv_timeout: float = DEFAULT_RECV_TIMEOUT,
strict_checksums: bool = True, strict_checksums: bool = True,
allowed_writes: frozenset = frozenset(),
) -> None: ) -> None:
""" """
Args: Args:
allowed_writes: write SUBs this connection may transmit. Empty by
default -- every write opcode in `micromate.opcodes` is refused
at `_send`, and `0xA2` is refused whatever this says.
strict_checksums: raise on a bad checksum. **Defaults to True, strict_checksums: raise on a bad checksum. **Defaults to True,
unlike the Series III sibling**, which logs and continues unlike the Series III sibling**, which logs and continues
because its parser cannot reliably tell an inner-frame because its parser cannot reliably tell an inner-frame
@@ -262,6 +270,7 @@ class MicromateProtocol:
self._transport = transport self._transport = transport
self._recv_timeout = recv_timeout self._recv_timeout = recv_timeout
self._strict = strict_checksums self._strict = strict_checksums
self._allowed_writes = frozenset(allowed_writes)
self._parser = MicromateFrameParser() self._parser = MicromateFrameParser()
self._pending: list[MicromateFrame] = [] self._pending: list[MicromateFrame] = []
@@ -509,6 +518,9 @@ class MicromateProtocol:
reset_parser=False) reset_parser=False)
def _send(self, frame: bytes) -> None: def _send(self, frame: bytes) -> None:
# The gate sees the bytes that are about to go out, not the caller's
# intent: every transmit in this package passes through here.
check_transmit(request_sub(frame), self._allowed_writes)
log.debug("TX %d bytes: %s", len(frame), frame.hex()) log.debug("TX %d bytes: %s", len(frame), frame.hex())
self._transport.write(frame) self._transport.write(frame)
+17
View File
@@ -468,6 +468,23 @@ def test_request_sub_refuses_anything_that_is_not_a_request_frame(junk):
request_sub(junk) request_sub(junk)
def _noncanonical_frames():
good = build_request(0x96, 0xFFFF)
return {
"interior raw 03": good[:5] + b"\x03" + good[5:],
"10 05 pair": good[:5] + b"\x10\x05" + good[5:],
"lone DLE before ETX": good[:-1] + b"\x10" + good[-1:],
"double 41 02 prefix": good[:2] + good,
"first byte not 0x10": good[:2] + bytes([0x11]) + good[3:],
}
@pytest.mark.parametrize("name", list(_noncanonical_frames()))
def test_request_sub_refuses_a_frame_that_is_not_in_canonical_form(name):
with pytest.raises(ValueError):
request_sub(_noncanonical_frames()[name])
@pytest.mark.skipif( @pytest.mark.skipif(
not _CAPTURES.is_dir(), not _CAPTURES.is_dir(),
reason="capture directory is gitignored; present only on a dev box", reason="capture directory is gitignored; present only on a dev box",
+75
View File
@@ -0,0 +1,75 @@
"""The send-side gate: no write opcode reaches the wire unless allowed, and 0xA2 never."""
from __future__ import annotations
import os
import sys
import pytest
sys.path.insert(0, os.path.dirname(os.path.dirname(os.path.abspath(__file__))))
import micromate.protocol as mm_proto # noqa: E402
from micromate.framing import build_request # noqa: E402
from micromate.opcodes import ( # noqa: E402
CROSS_SERIES_COLLISIONS, WRITE_SUBS, OpcodeRefused, check_transmit,
)
from test_micromate_protocol import frame, proto # noqa: E402
# THOR's captured end-call-home frame -- byte-identical to Series III's CONFIRM ERASE.
A2_WIRE = bytes.fromhex("4102101000a200ffff00000000000000000000b003")
def test_no_read_command_is_classed_as_a_write():
reads = {v for k, v in vars(mm_proto).items() if k.startswith("SUB_")}
assert reads and not (reads & set(WRITE_SUBS))
def test_0xa2_is_a_collision_and_a_write():
assert 0xA2 in CROSS_SERIES_COLLISIONS and 0xA2 in WRITE_SUBS
def test_a_write_is_refused_unless_allowed():
with pytest.raises(OpcodeRefused, match="0x96"):
check_transmit(0x96)
check_transmit(0x96, frozenset({0x96}))
check_transmit(0x5B) # a read needs no permission
def test_0xa2_is_refused_even_when_allowed():
with pytest.raises(OpcodeRefused, match="ERASE"):
check_transmit(0xA2, frozenset({0xA2}))
def test_the_protocol_refuses_a_write_and_writes_nothing():
p, t = proto([])
with pytest.raises(OpcodeRefused):
p._exchange(0x96, offset=0xFFFF)
with pytest.raises(OpcodeRefused):
p._send(build_request(0x97, 0xFFFF)) # a direct _send is gated too
assert t.written == []
def test_the_protocol_refuses_the_captured_0xa2_frame_byte_for_byte():
p, t = proto([], allowed_writes=frozenset({0xA2}))
with pytest.raises(OpcodeRefused):
p._send(A2_WIRE)
assert t.written == []
def test_an_explicitly_allowed_write_goes_out_on_a_scripted_transport():
p, t = proto([frame(0x69, bytes(11))], allowed_writes=frozenset({0x96}))
p._exchange(0x96, offset=0xFFFF)
assert t.written == [build_request(0x96, 0xFFFF)]
def test_reads_are_unaffected_by_the_gate():
p, t = proto([frame(0xA4, bytes(11))])
p.poll()
assert len(t.written) == 1
def test_a_frame_that_is_not_a_request_is_refused_not_sent():
p, t = proto([])
with pytest.raises(ValueError):
p._send(b"\x41\x03")
assert t.written == []