docs: the first commands this project originated -- start/stop on UM20147

Bench, 2026-10-25, Brian's go per send: 0x96 acked in 464 ms and read back
monitoring at the first 2 s poll (during the sensor check); 0x97 acked in
116 ms, then 0x49 read a new value 0x01 for ~18 s (inferred: the unit's
call-home attempts after a stop) before idle; two stops to an idle unit acked
in 10 ms and changed nothing.  Retracts "no command has ever been originated"
in place in CLAUDE.md and the reference's untested list; answers the spec's
stop-while-stopped question.

Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
This commit is contained in:
serversdownandClaude Opus 5.5 committed 2026-10-25 15:56:18 -04:00
1 parent b1c87ecccd
commit 4b911b1c0c
3 files changed
+135 -7

No files matched your search

+112 -2
View File
@@ -2217,6 +2217,13 @@ having: nothing else read so far reports the unit's own time.
↑ data[11]: 0x02 monitoring, 0x00 idle
```
> **Amended 2026-10-25.** There are four values now. `0x03` is a call-home
> session; see *Correction: `SUB 0x49` has a third state value*. `0x01` reads
> for about 18 s after a stop; its meaning is inferred to be a call-home attempt
> that has not connected. See *The first commands this project originated*.
> `0x02` was also read 2.5 s after a start, while the screen showed the sensor
> check.
**A second monitoring indicator, in a 21-byte response instead of `0x1C`'s 60.**
Different encoding from `0x1C`'s flag (`0x02` vs `0x0E`), so they are separate
fields, not the same byte read twice. For a polling client this is the cheaper
@@ -4165,8 +4172,108 @@ assumed:
device will not stop it and the ack will not distinguish it. That guard has
to live in SFM.
## ✅ The first commands this project originated: start and stop on UM20147 (2026-10-25)
These were the first frames this project ever sent to a unit that change its
state. Every write before this one was THOR's, recorded while we watched. Brian
gave a go at the bench for each send.
**Setup.**
- **Unit:** UM20147, firmware `11.0BD` (Thor line, reply flags `0x03`), on USB
CDC-ACM `/dev/ttyACM0`.
- **Sensors:** none attached.
- **Active setup:** `BENCH01`.
- **Sender:** SFM's `POST /device/monitor/start|stop?serial=UM20147` (branch
`feat/series4-sfm-parity` at `b1c87ec`), with every TX frame and every
validated RX frame logged at millisecond resolution.
- **Path:** each send went through the phase-3 safety core in this order:
1. a fresh serial read;
2. a `0x49` state read;
3. the audit row written;
4. one `execute()`;
5. read back every 2 s.
### What was sent and what came back (measured)
| time (EDT) | sent | ack | ack latency | `0x49` content[0] afterwards |
|---|---|---|---|---|
| 15:43:47.430 | `0x96` `41021010009600ffff00000000000000000000a403` | `0x69`, 11 zero bytes | **464 ms** | `0x02` at the first read, 2.0 s after the ack |
| 15:45:51.922 | `0x97` `41021010009700ffff00000000000000000000a503` | `0x68`, 11 zero bytes | **116 ms** | **`0x01` on all 9 reads from +2.1 s to +18.2 s**, then `0x00` from +20.3 s |
| 15:52:42.645 | `0x97` (unit already idle; `even_if_already`) | `0x68`, 11 zero bytes | **10 ms** | `0x00`, unchanged |
| 15:53:51.871 | `0x97` (idle again, screen watched) | `0x68`, 11 zero bytes | **10 ms** | `0x00`, unchanged |
- **The frames.** Both are THOR's own bytes, offset `0xFFFF` included. The phase-2
bench question "is offset `0x0000` honoured" was not tested and does not need
to be.
- **`0x1C` `data[12]` agrees.** It read `0x00` idle before the start, `0x0E` at
the start's read-back and at the stop's preamble, and `0x00` again at +20 s.
`0x0E` is the same monitoring value UM12947 showed on 2026-09-24. `0x1C` was
not read during the `0x01` window.
- **The start's screen** showed a sensor check, then monitoring. With no sensors
attached, the check passed without complaint (Brian, watching).
- **The start's state.** `0x49` already read `0x02` at +2.5 s, so the state
byte very probably reads monitoring *during* the sensor check. That is
inferred, not measured: the check's length on screen was not timed.
Consequence: a second start sent during the check would see "monitoring" and
be skipped, not sent.
- **One histogram was recorded and closed.** The event is timestamped
15:44:01, 14 s after the start, which is roughly the length of the sensor
check. The event count went 5 → 6 at the stop (`UM20147_20261025154401.IDFH`,
7,976 B).
- Its peaks are 0.00186 in/s on all three channels, identical, because no
sensors were attached.
- Free memory fell 4,096 B at the start and another 4,096 B by the stop. The
same 4 KiB step was seen in the 2026-09-24 session.
- **The stop's screen.** The unit tried to call home right after the stop. Brian
says it always does this when taken out of monitor mode. It never connected,
because it has no modem, and it ran out of attempts. A watch of `0x49`
once a second from 15:47:19 to 15:49:50 read `0x00` throughout.
- **A stop sent to an idle unit is harmless.** It was acked in 10 ms, twice.
Nothing changed: not the state, the event count, free memory or the screen,
and there was no call-home attempt. The ~10x shorter ack suggests the
firmware skips its close-down work. This settles the spec's open question
"what does a stop-while-stopped do".
### 🔶 `0x49` content[0] = `0x01`: a fourth state value (value measured, meaning inferred)
The values are now `0x00` idle, `0x02` monitoring and `0x03` in a call-home
session (10 of 10 reads, 2026-10-14). The new one is **`0x01`, for about 18 s
right after a stop**.
**Inferred meaning: a call-home *attempt* in progress, dialling and not
connected.** It is distinct from `0x03`, a call-home *session* that has
connected. The timing fits: the `0x01` window opened 2 s after the stop, on
screen the unit was trying to call home, and it closed when the attempts ran
out.
**Not excluded:** `0x01` could instead mean "stopping, closing the record", with
the call-home attempts overlapping it. Two tests would separate them:
- a stop with call-home-after-event switched off;
- a stop on a unit whose modem connects, where the inference predicts
`0x01` → `0x03`. This fits into the ring-path Run A/B.
**What SFM does with it.** `read_run_state()` names it `unknown(0x01)`, so the
change path refuses any start or stop in that window ("never been measured --
nothing sent", HTTP 409). That is deliberate: name it only once its meaning is
measured. The stop's read-back simply kept polling through it, because `0x01`
is not idle, and the stop verified at +20 s, well inside the 60 s window.
### Audit rows (SFM `device_commands`, scratch bench DB)
All four rows read `outcome=sent`, `verified=ok`, `sent=1`, caller
`bench-brian`. Their `states` columns:
- **start:** `idle → [idle, monitoring] → monitoring`
- **stop:** `monitoring → [monitoring, 9 × unknown(0x01), idle] → idle`
- **the two forced stops:** `idle → [idle, idle] → idle`, each carrying the note
that the read-back cannot show the send changed anything.
## ⚠ Untested and unsafe-until-agreed
> ✅ **Retracted in part (2026-10-25):** the opening line below was true until
> 2026-10-25. Start and stop (`0x96` / `0x97`) have now been **originated by
> SFM** against UM20147. See *The first commands this project originated*. Every
> other item in this section remains never-sent.
**Nothing below has been sent to a unit by us, and nothing should be without an
explicit decision.**
@@ -4183,12 +4290,15 @@ is known; our encoder is unwritten and unproven.
`0x55`. **Destructive.** Series III's `0xA3`/`0xA2` erase-all has *not* been
seen on Series IV and may not exist
- **Start / stop monitoring** (`0x96` / `0x97`) — observed via Thor 2026-09-24,
acks `0x69` / `0x68`
acks `0x69` / `0x68`. ✅ **Originated by SFM 2026-10-25** on UM20147 (4 sends,
all acked and verified) — no longer untested
- **Scheduler enable** (`0x47`) — observed; `params[7]` semantics still unclear
Every one of these is now *observed*. **None has ever been originated by us**,
and that is the line that still matters: the wire format is known, our encoder is
unwritten and unproven.
unwritten and unproven. *(2026-10-25: true still of every item here except
start/stop, which SFM originated at the bench — see the retraction note at the
top of this section.)*
- `0x1F` (advance event pointer) — non-destructive on Series III but it does
move device state, so it is parked with the rest