docs(series4): OBSERVED -- THOR's ACH side is POLL, byte-identical to ours

First capture of THOR's half of a Micromate call-home, taken with ach_mitm.py
between UM12947's modem and a THOR 1.5.0.29 ACH server on port 8070.

THOR sends POLL (SUB 0x5B, offset 0x0030) and NOTHING ELSE -- four times over
~21 s, then gives up.  No greeting, no answer to the RADIO RING, no CONNECT.

And that POLL is BYTE-IDENTICAL to what micromate.protocol builds:
build_request(SUB_POLL, 0x0030) reproduces all four frames exactly.

So the ACH session is PULL, and bridges/mm_ach_server.py already implements it
correctly.  The "inbound call-home session" -- carried for weeks as the last
protocol unknown -- was never a separate protocol at all.  It is the ordinary
command set on an inbound socket, exactly as series III's 72 captured sessions
suggested it would be.

THE OPEN PROBLEM IS NOW CLEARLY ELSEWHERE.  In the same capture the unit sent
only "RADIO RING", four times, and never a protocol frame.  THOR polled four
times and got nothing -- identically to our own server in three attempts the
same afternoon.  THE VENDOR'S OWN SOFTWARE FAILS THE SAME WAY WE DO, which
eliminates the receiver as a suspect and places the fault between modem and
unit.

Established: cellular healthy (151 ms connect, outbound dial works), bytes do
reach us from the unit's side, modem serial config matches spec (115200 8N1, no
flow control, PAD/TCP), cable is FTDI and cold-booted with it attached.  Not
established: whether the unit or the modem emits "RADIO RING" -- it is the
literal string in this unit's own 0x2C dial-string field, and the cheap
disambiguation is to disconnect the unit and see if it still appears.

Next step is a config diff against a working deployed unit's modem, not more
protocol work.

Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Ru8Lg9HkkYvX9VWWo65SmL
This commit is contained in:
serversdownandClaude Opus 5 committed 2026-10-14 16:42:18 -04:00
1 parent fc0a7b2a88
commit 52d18b0d5d
1 file changed
+51 -1
+51 -1
View File
@@ -2308,7 +2308,57 @@ events (already solved — `0x08`/`0x1E`/`0x0A`/`0x5A`), keep our own high-water
mark, and *optionally* erase. **The erase opcodes are the only genuinely missing
piece**, and they remain on the unsafe list.
### The session is server-driven
### ✅ OBSERVED 2026-10-14 — THOR's ACH side, and it is POLL
First capture of THOR's half of a Micromate call-home, via `ach_mitm.py` between
UM12947's modem and a THOR 1.5.0.29 ACH server on port 8070.
```
unit -> THOR 60 B " \nRADIO RING \nRADIO RING \nRADIO RING \nRADIO RING"
THOR -> unit 84 B 4 x 41 02 10 10 00 5b 00 00 30 00 00 00 00 00 00 00 00 00 00 9b 03
```
**THOR sends `POLL` (`SUB 0x5B`, offset `0x0030`) — and nothing else.** Four
times over ~21 seconds, then it gives up. It does **not** send a greeting, does
not answer the `RADIO RING`, does not send `CONNECT`, and does not wait to be
spoken to beyond its initial silence.
🔑 **That POLL is byte-identical to the one `micromate.protocol` builds.**
Verified: `build_request(SUB_POLL, 0x0030)` reproduces all four frames exactly.
**So the ACH session is pull, and our receiver already implements it correctly.**
`bridges/mm_ach_server.py` does what THOR does. The "inbound call-home session"
was never a separate protocol — it is the ordinary command set on an inbound
socket, exactly as Series III's 72 captured sessions suggested.
### ⚠ But the unit answered neither — and that is the open problem
In the same capture the unit sent **only** `RADIO RING`, four times, and never a
protocol frame. THOR polled four times and got nothing. Our own server, in three
earlier attempts the same afternoon, saw the identical thing.
**The vendor's own software fails the same way we do**, which eliminates the
receiver as a suspect and places the fault between the modem and the unit.
What is established about that fault:
| | |
|---|---|
| cellular link | ✅ healthy — TCP connect in 151 ms, outbound dial succeeds |
| modem → us | ✅ bytes arrive |
| unit serial TX | ✅ *something* reaches us — the `RADIO RING` text |
| unit protocol mode | ❌ never entered; no frame ever sent |
| cable | FTDI, physically checked, cold-booted with it attached |
| modem serial config | 115200 8N1, no flow control, PAD/TCP — matches spec |
⚠ `"RADIO RING"` is **the literal string in this unit's own `0x2C` call-home
config** (the 40-byte dial-string field). Whether the unit emits it or the modem
does is **not yet established** — the cheap disambiguation is to disconnect the
unit and see whether the string still appears.
**Next step is a config diff, not more protocol work.** The deployed fleet runs
call-home over PAD successfully, so a working unit's modem settings are the
reference. Compare them against this one.
Which matches the firmware's state machine and its
`CMD_EXIT_CALL_HOME_DELETE_EVENTS_START_MONITORING` /