BE9441 on a serial cable (bench, 2026-10-25) twice sent "Operating System"
~3 s after the port opened and ignored the POLL sent before it; the request
then failed at the full receive timeout (502 after 15 s on /device/info, 504
after 120 s on a download). After a mid-download reboot it answered 8.8 s
after its banner -- the one measured readiness point.
startup()'s first POLL now stops waiting the moment the banner arrives (that
POLL will never be answered) and polls again every 2 s for up to 20 s. Without
a banner nothing changes: a silent unit fails at the normal timeout, with no
re-polling. Only SESSION_RESET and POLL are sent, so this is safe in front of
the change path too.
No codec, store or DB change.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44