- micromate reference: the watchdog can check every 5 s, hourly or never
(Brian, operator-reported). The 10-14 "reconnects continuously" describes
that THOR's setting, not fixed behaviour; whether a check holds the line,
and how a call-home reaches THOR with the watchdog off, are unmeasured.
- spec, ring-path test: the old setup ("a unit THOR is not otherwise
watching") would not test the production path, since THOR receives a
call-home on its own connection. Revised: UM20147 as a THOR test unit; Run 0
baseline with the watchdog off; Run A with SFM holding the line; Run A2 and
Run B at the fleet's watchdog setting; after the 1c bench pass.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
- CLAUDE.md: a 1c entry under Where things stand (serial mode, what follows
the unit's own answer, writes off until phases 4-5, the Node-run page tests)
and the legacy-route guard in the REST API notes, with why the stop tools
are exempt.
- Spec: the 1c build status; the ring-path Runs A/B are still owed before
serial mode is used on a unit that calls home to THOR; which parked 1c items
the page settles (CORS: same origin; the S4 mic is not shown).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Review of b5037b0 (measured on 12 recorded SFM compliance reads): the read
keeps three escape bytes from its reply headers, so every real config image is
refused by write_image -- correctly, but only after 68 and 73 had been sent,
with a message saying nothing was. All four blocks are now checked first; the
test feeds the block exactly as SFM's read produces it and asserts no frame is
sent (two went out without the check).
Config push stays unusable on purpose: fixing that read alone would let the
compliance encoder write some fields to the wrong bytes (e.g. 4,096 sps as
4,112) while the image still passes. The rework -- logical read, encoding at
measured offsets with #48, a diff check, N pinned per SUB, an idle check, the
start/stop safeguards on POST /device/config -- is recorded in the spec and on
#46. Start/stop frames are unchanged (verified byte-identical by the review).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Brian: stopping by command or keypad with ACH enabled makes the unit call home
and upload events + MLG, which can take minutes. Fits UM20147's 0x01 after a
stop (10-25). Owed: measure a MiniMate stop with ACH on, through the bridge.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Follow-ups from the review of 887e75d (verdict: keep, with fixes; no critical).
- The cap: a caller's max_chunks (client.py passes 128) now bounds only a walk
whose end is unknown. With STRT it cut every event past ~66 KB short --
2,545 of 63,500 archived histograms are bigger (the review's count, DL2).
Strict raised; legacy sent a TERM for most of the event, or a bare ValueError.
- A STRT claiming less than one 0x200 chunk, or more than 4 MiB (a sanity bound,
not a measured limit), is refused as a misread, in both modes -- once a bare
ValueError and a 500.
- TERM is sent only for a true tail (< 0x200). After an early end the legacy
walk returns what arrived and sends none.
- build_5a_request wraps build_bw_frame; the old 5A helpers are marked
superseded (kept for tests/test_5a_protocol.py) and their imports dropped.
Tests: all 8 recorded events (were 4) walk exactly as Blastware and rebuild its
own files; an end key holding escaped bytes; a 300 KB event past a 128 cap; both
misread-STRT refusals; the 1A frames BE9441 answered post-fix; the checksum
vectors retargeted. Mutants the review saw survive (no STRT un-escape; a
standard-request escape revert) and 3 new ones are each caught.
Measured on the way: a reply's checksum is SUM8 of its unescaped payload,
748/748. The 'S3 checksums frequently fail' note was the parser summing its
own kept escape bytes; noted, parser unchanged.
Docs: the crossing count corrected to four (events 1, 3, 5, 7); the remaining
stale 5A sections in CLAUDE.md annotated; the write-frame suspicion recorded as
inferred only. No codec, store or DB change.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
CLAUDE.md: the KNOWN BUG entry marked fixed (887e75d) with what settled it, and
retraction notes under the 5A sections that described the misreading (partial
stuffing, offset_hi 0x10 raw, 11-byte params, metadata pages 0x1002/0x1004).
Series-III reference: a 2026-10-26 (3) row. Spec: the MiniMate check updated.
Code comments that called the page bug open, updated; the adapter's struct.error
mapping kept as a defence, its message and test no longer naming the old bug.
Verified live on BE9441 the same day: all 8 events downloaded by serial, the 4
that cross a 64 KB page included, each whole and matching the unit's own peaks.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Brian's Blastware downloads of BE9441's 20 events give ground truth. SFM's
re-run downloads of events 0, 1, 3, 4 and 10 are byte-identical to Blastware's
own files; imported first through the watcher route, the same events download
as already_stored (no duplicate rows -- the unit's 0C and Blastware's file agree
on serial + timestamp). Fixtures: Blastware's P00/Q10 (now asserted equal to
SFM's builds) and QZ0/T80, the two page-crossing events, as byte-exact targets.
The 64 KB page bug, narrowed by a read-only test walk: carrying the page byte
addresses the first chunk in page 0x12 (answered), but the next request carries
a raw 0x03 inside its params (counter 0x032c) and gets no reply. Pages after
0x11 have such counters; 0x11 does not (event 1 skips 0x0000-0x05FF). Needs a
Blastware wire capture of event 2 or 19 (recorded in CLAUDE.md, the Series-III
reference and the spec). No code change.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Series-III reference: a 2026-10-26 row (5A checksum escape, measured), and the
2026-10-25 row's guessed cause of the mid-download reboot (battery, firmware)
retracted in place -- it was our request. CRLF kept. Spec: the re-run, item
by item, and what is still owed. CLAUDE.md: the phase-1b bullet brought up to
date.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Re-review of 64273c0: nothing pinned the TERM skip -- a TERM cut one byte off
loses a byte after the END record, invisible to every decode and peak check.
Golden sha256 of both fixtures' bodies and written files (event 0's file is
byte-identical to the one SFM stored at the bench before any fix; event 1's is
the bench's 25,810 bytes plus the 2 recovered), and a TERM moved to 0x1002.
The clipped-blast test now sits two steps past full scale (32032 counts), so it
needs the carve-out. Spec: the TOOL_VERSION reason corrected (no stored file
is affected); a MicL-only waveform is now refused -- failing safe, bench-check.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
3898d03 rewrote docs/instantel_protocol_reference.md with LF endings (a 7,327-line
diff for 3 added lines). CRLF restored; the file's real change is the 3 lines.
Also: BE9441's 21,504 samples are 5 s record + 0.25 s pre-trigger at 4096 sps,
not '+ 1 s' (reference row, fixture README, test comment).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Series-III reference: the 0x15 serial is a C string (BE9441's "BE9441\x00?"),
A5 replies echo their address at data[2:6] (metadata pages only on the
event-1 walk), the unit boots on serial-port open (banner ~3 s, answered 8.8 s
after a reboot's banner), one mid-download reboot, and 24 index entries vs 20
listed events (inferred: monitor-log entries). Spec: the MiniMate check's
first run, item by item, and what is still owed. CLAUDE.md: the phase-1b
"unproven" line retracted in place, with the four bugs and the re-run owed.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
4b911b1 (and its subject line) called UM20147's start/stop "the first commands
this project originated". The retracted CLAUDE.md line was always about Series
4: the minimateplus stack has sent Series-III writes (start/stop, config push,
erase, call-home config) since April 2026. Narrowed in CLAUDE.md and the
Micromate reference.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Bench, 2026-10-25, Brian's go per send: 0x96 acked in 464 ms and read back
monitoring at the first 2 s poll (during the sensor check); 0x97 acked in
116 ms, then 0x49 read a new value 0x01 for ~18 s (inferred: the unit's
call-home attempts after a stop) before idle; two stops to an idle unit acked
in 10 ms and changed nothing. Retracts "no command has ever been originated"
in place in CLAUDE.md and the reference's untested list; answers the spec's
stop-while-stopped question.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
- New section "Left open by the phase 1b review (2026-10-21)", after the
1a one: twelve one-line items, each naming the phase it matters to
(retry re-running a whole download, last_used after a kept-line error,
verified:null's two meanings, mic naming + the S4 0x0C mic denormal,
500 detail text, the serial as a directory name, no server-level ring
test, S3 stored record_type, a fresh S4 download's gaps, orphan files,
same-second collisions, 423 Retry-After).
- The 1b bullets now give the owed MiniMate bench check's scope: a 3+
event list (1F(browse) after 1E(arm) without 1F(arm)), a non-first
event, a histogram (capture its 0C), an event past 64 KB (the named
502), a stale id (no 5A), and a dropped reply via mm_link-style fault
injection.
- The 1b "Download" bullet's "refreshes the row" is retracted in place:
the final review changed it to "returns the row, writes nothing".
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Ten tasks, test-first: the is_open fix, two client reads, core types, the
per-unit lock, both adapters, Series-4 sessions with ring safety,
DeviceAccess with the reaper and the contract tests, the endpoints, and a
read-only bench check on UM20147.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Nothing breaks between phases: the shared models apply when a request names
the unit by serial, and the legacy Series-3 path stays as it is until the
webapp (1c) and watch_unit.sh move over.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Brian's principle: talking to a Series 3 or a Series 4 unit is identical for
the user; only the serial prefix and each model's settings differ, and the
adapters absorb the rest.
Five places the draft broke it, now fixed: units are named the same way
(serial + address, no-serial kept only as a legacy Series-3 path); one set
of series-neutral response models with series-only fields under `detail`;
one opaque event_id for both; a uniform 501 "not supported for Series N
yet" instead of missing routes; and the webapp brought into scope with the
same screens for both. Adds an adapter table, contract tests that keep the
two adapters honest, and notes that existing Series-3 response shapes move
to the shared models (the webapp updates with them; Terra-View does not
call /device/*).
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
Parity of jobs with Series 3 for regular comms and settings (identify,
status, settings, events, download, monitor log, start/stop, call-home
enable/disable, setup push); Series-4 emergency tools deferred. A single
device-access layer: series from the serial prefix, identity confirmed
before any write, a per-unit lock, an 0xA2 opcode guard, read-back
verification of every change, distinct error codes, and an audit table.
Series-4 sessions ("stay on the line") now; Series-3 sessions after a bench
test of MiniMate hangup/DCD behaviour.
Includes the fix list found in the 2026-10-19 inventory, the to-be-added
table, and the RX55 container idea as a parking-lot item.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
23 more snapshots of UM20147, keypad-driven.
MEASURED: loading a .MMB replaces the active config byte-for-byte -- three
loads, each moving exactly the fields that differ, the loaded block identical
to the file's saved state, no load marker. The setup name's spelling
(.MMB/.mmb) depends on whether it was saved or loaded.
MEASURED: job number [40:42], report flags [39] (0x02 job no., 0x08 scaled
distance; 0x01 unknown); distance [30:34] in metres and charge weight
[34:38] in kg, converted bit-exactly with ft / 3.2808 and lb / 2.21 -- the
firmware's own constants, not the textbook ones. Scaled distance is not
stored. Location confirmed at [144].
MEASURED: 0x08 is the preferences block (display units at content[31]),
not an event index; switching units moves nothing in 0x1A. 0x1A, 0x08 and
0x2E share one checksum rule (N = content[0:2]; CRC over [0:N-2] at
[N:N+2]); 0x2C has none. 0x2C session timeout is at [118:120], encoding
unknown; modem baud is in none of the six blocks.
CORRECTED IN PLACE: the 9-24 notes-label offset (0x8A -> 0x7A) and
channel-block start (0x06BC -> 0x06AC), both 16-byte slips.
RULE: never write modem baud or modem type remotely -- the remote link is
the modem port.
No codec, store or DB change; no backfill.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
47 snapshots of UM20147 while settings were changed on its own keypad, one
at a time. Every byte that moved is accounted for; nothing outside 0x1A
moved.
MEASURED (operator named setting + values): record mode [5] (01 Waveform,
02 Manual, 03 Histogram, 04 Combo -- S3's encoding, one byte later than the
S3 analogy put it), sample rate [6:8], histogram interval [8:10] s,
pre-trigger [12:16] f32 negative s (all four values), stop mode [17], record
time [18:22] f32, auto-stop [23], active-sensor and trigger-source bitmasks
[25]/[29], trigger level at channel +30 (geo in/s, mic psi).
MEASURED: the trailer is CRC-16/AUG-CCITT over content[0:2088] -- 47/47 and
a second unit. Thor's write omits it, so it is read-side integrity, not a
write obligation.
MEASURED: blocks 1-3 are geophones, block 4 is the ACTIVE mic (a byte copy
of 5 or 6), 5 and 6 are the stored linear / SLM mic setups. No separate
mic-type byte; block 4's +4:8 code is the type. Promotes the 10-15 "+4
channel type" guess; retracts "+46:48 is a trigger-source flag" in place.
MEASURED: 0x1A reads the keypad's edit buffer live; discard reverts;
commit timing differs by widget (list / spinner / sub-window).
INFERRED, Series III: the 6-byte "stable anchor" sits exactly where Series
IV keeps pre-trigger (-0.25 s) + stop mode (Fixed). An S3 unit in Auto
stop mode would lose it and decode no mode/rate/interval/record time. Not
measured on S3; noted in instantel_protocol_reference.md, code untouched.
No codec, store or DB change; no backfill.
Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01SyJ2ip3Krb6dtdv2cXua44
and two are guesses
Six 48-byte channel blocks at content[1708], stride exactly 48: Tran, Vert,
Long, Mic, LMic, SMic. (Mic is 3 chars, so a 4+-printable scan misses it and
the stride looks like 96 across that gap.)
RECORDED IN THREE EXPLICIT GRADES, because I wrote them in one voice first and
that is the failure mode this reference already carries retractions for -- the
0x0C float from a single sample, the cost model fitted to sub-1 KB responses,
offset detector v1. All three were an interpretation presented with the
confidence of a measurement.
MEASURED, and the one worth having: channel+24 is a float32 BE reading
3.1030800342559814 on all three geo channels. Divided by 10,000 that is
0.00031030800342559815 -- the documented _GEO_LSB_IPS to 1.1e-8. It implies
10.0/3.10308 = 3.222605 V full scale, which at 10,000 counts/V gives 32226.05
counts, the documented figure exactly.
That is an INDEPENDENT confirmation of a number that until now rested purely on
statistical inference: _GEO_LSB_IPS was pinned by intersecting 991,415 rounding
constraints from Thor's own CSV exports. The unit reports it directly. Two
unrelated derivations agreeing to eight digits. It is also almost exactly half
Series III's 6.206053 (ratio 1.99997, the residual being S3's rounded display
value).
Also measured: the units strings ("in."/"/s.", "psi"/"(L)", "dB"/"(A)") are
literal ASCII, and Tran/Vert/Long are byte-identical EXCEPT +47, which reads
0x01 on Tran and Vert and 0x00 on Long.
INFERRED (one setup, one unit): that +24 is the calibration constant rather than
another field holding the same number -- the arithmetic proves the number, not
the field's purpose; and that +47 is an enable or trigger-source flag.
GUESSED, explicitly flagged not to build on: +4 as a uint32 "channel type", from
six correlated observations in a single setup; and +8:24 as eight uint16 BE
values, where the split itself is an assumption.
TOOLING FIX in the same commit, from a real miss: the volatile baseline ran four
reads over eight seconds, so it never crossed a minute boundary and never saw
the minutes byte. Five "changes" then came in a row that were just the clock.
Hours and the date would have slipped through identically. An empirical noise
floor only catches what moves WHILE sampling, so 0x1C's known clock span
(content[2:10]) is now seeded regardless, and the report says which bytes were
observed versus seeded. Memory-free is deliberately left unmasked -- it moves
only when the unit records, which is worth being told about.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Ru8Lg9HkkYvX9VWWo65SmL
The Series III config map was built by changing one setting and seeing which
bytes moved. Whether that method transfers to Series IV depended on an
unmeasured question: how much of a config block moves ON ITS OWN. If a block
carries a clock or a counter, every diff arrives polluted and there is no way to
tell the real answer from the noise in a single pair.
MEASURED ON UM20147 (11.0BD), FOUR READS BACK TO BACK, NOTHING TOUCHED:
0x1A compliance 2103 B 0 bytes moved
0x2C call home 137 B 0
0x2E trigger 39 B 0
0x08 event index 101 B 0
0x01 device info 163 B 0
0x1C monitor status 59 B 2 (and those two are explained below)
Every config block held every byte still, so the method transfers directly and
needs no noise floor subtracted. That was the open question.
scratch/mm_config_diff.py drives it: `volatile` establishes the floor, `snap`
saves a labelled read of all five blocks, `diff` reports changed runs with each
plausible field interpretation (u8/u16be/u32be/f32be) and reports any volatile
bytes separately rather than silently hiding them.
CORRECTION TO content[6] OF 0x1C, long recorded only as "NOT the hour": it is a
sub-second tick, ~4020 counts/second in steps of exactly 4, wrapping at 256 --
about a 64 ms period, consistent with the low 6 bits of a millisecond counter.
Consequence worth knowing: a 0x1C block is never byte-identical to itself, so
any "has the status block changed?" check answers yes ~15 times a second.
Compare named fields, never whole blocks.
I nearly recorded that byte wrong, and the trap is cheap enough to document:
sampled once per second it reads as a smooth monotonic counter at ~16/s with a
16-second wrap. Twelve consecutive samples supported it. It is aliasing -- a
64 ms counter read once a second is noise that happens to look tidy. Measure a
counter back to back before trusting any rate from spaced samples.
Also: the settings do not have to be changed from THOR. The unit's own keypad
works, which needs no Windows VM and does not contend for the modem's single
TCP session.
Co-Authored-By: Claude Opus 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_01Ru8Lg9HkkYvX9VWWo65SmL